1 / 5
| PV DC BUD-40/3 Surge Protection Device | ||
|---|---|---|
| Pole | 3P | |
| Standard | EN 61643-31 | |
| Electrical Characteristics | ||
| Category IEC/EN | IEC II/EN2 | |
| Open Voltage Uoc Max | 1000V DC | |
| Max Continuous Operational Voltage Ucpv | 1000V DC | |
| Nominal Discharge Current In (8/20)μs | 20KA | |
| Maximum Discharge Current Imax (8/20)μs | 40KA | |
| Voltage Protection Level Up | ≤3.8KV | |
| Response Time | ≤25ns | |
| Control and Indication | ||
| Operating State/fault Indication | Green/Red | |
| Remote Signalling Contact (Optional) | Max. Working Voltage(V) | 30V DC |
| Max. Working Current | 1A | |
| Connection and Installation | ||
| Wire Range | Hard cable mm² | 4~25 |
| Flexible cable mm² | 4~16 | |
| Terminal Screws | M5 | |
| Torque (Nm) | Main Circuit | 2.5 |
| Remote Contact | 0.25 | |
| Degree of Protection | IP20 | |
| Installation Environment | ||
| Operating Temperature Range (TU) | -40°C~+80°C | |
| For Mounting on | TH35-7.5/DIN35 | |
| Relative Humidity | 30%~90% | |
| Weight kg | 0.36 | |